Conduit Fill Calculator (NEC Chapter 9)
Conduit fill percentage check. User enters cross-sectional areas — verify against NEC Ch 9 Tables 1, 4, 5.
ESTIMATE ONLY — not a stamped engineering design. Verify with a licensed PE or licensed electrician before procurement or construction. This tool contains no NEC table values. You enter the conduit interior cross-sectional area (NEC Ch 9 Table 4) and each conductor area (NEC Ch 9 Table 5) yourself.
Conduit
Informational only.
Informational only.
See NEC Chapter 9 Table 4 for the interior cross-sectional area of your conduit type and trade size. Enter the total area (100% column) here.
See NEC Chapter 9 Table 1 for the maximum fill percentage based on the number of conductors. The widely-applied default for >2 conductors is 40% (the "40% rule"). Single-conductor and two-conductor installations, plus short nipples (≤24 in), use different limits — consult Table 1 directly and enter the appropriate value here.
Conductors
For each conductor type/size used in this conduit, add a row. See NEC Chapter 9 Table 5 for the cross-sectional area of each conductor (insulation included). Enter that area in the row.
Fill Status
OK
0.00% fill (at or below 40% target)
Remaining Capacity
0.0000
sq in available
| Conduit interior area | 0.0000 sq in |
| Total conductor area (Σ count × area) | 0.0000 sq in |
| Allowable area at 40% fill | 0.0000 sq in |
| Actual fill % | 0.00% |
Methodology
Total conductor area = Σ (per-conductor cross-sectional area × count) across every row. Allowable area = conduit interior area × target fill % ÷ 100. Actual fill % = (total conductor area ÷ conduit area) × 100. Reference standard: NEC Chapter 9 — Tables 1 (Percent of Cross Section of Conduit and Tubing for Conductors), 4 (Dimensions and Percent Area of Conduit and Tubing), and 5 (Dimensions of Insulated Conductors and Fixture Wires). No NEC Chapter 9 table values are hardcoded in this tool — you supply the conduit interior area, each conductor area, and the target fill percentage yourself.